站内搜索
|
详细信息 Product Name: UL Ce Approved 200A Split Core Current Transformer Model NO.: ECS25 Voltage Transformation Principle: Electromagnetic Type Magnetic Circuit Structure: Single Stage Type Installation: Penetration Type Insulating Medium: Common Insulating Materials Winding Form: Single Layer & Tightly Wound Type Usage: Measurement Operation Condition: Indoor Phase: Single Type: Current Transformer Application: Instrument Trademark: ECHUN Transport Package: 48PCS/Box Specification: CE/RoHS/UL Origin: Dongguan Guangdong China HS Code: 8504500000 Product Description 200A Split Core Current Transformer UL CE ApprovedThe ECS25 series are split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These CTs can be mounted without removing existing cables for easier installation.Electrical specifications:Rated primary current: 50/60Hz: 200nom(1~300A max)Turn ratio: Np: Ns= 1: 3000Current ratio: 200A/66.6mAD. C. Resistance at 20: 150Accuracy @RL5 : 0.5%Linearity @RL5 : 0.2%Phase error at rated current range: <1 degreesOperating temperature range: -40 to 65 degreesStorage temperature range: -45 to 85 degreesDielectric withstanding voltage (hi-pot): 2.5kV/1mA/1minInsulation resistance: 500V DC/100M MinApplications: Current measurement, monitoring & protectionAdvantage:Low cost;Mount easy;Excellent linearity over the whole range;Fully RoHS compliant.
|